.. _everest_modules_handwritten_Bender_isoCHA425HV:
|
||||
|
||||
.. ******************
|
||||
.. Bender_isoCHA425HV
|
||||
.. ******************
|
||||
|
||||
IMD driver for Bender isoCHA IMD devices
|
||||
|
||||
Default settings
|
||||
================
|
||||
|
||||
By default the Bender IsoCHA type insulation monitor devices come pre-configured with the following settings:
|
||||
|
||||
* 19200 baud / even parity / 1 stop-bit
|
||||
* bus address: 3
|
||||
|
||||
If you want to change those settings, you need to use the manufacturer's configuration software or change the settings on the device's LCD display and buttons.
|
||||
|
||||
Bus termination
|
||||
----------------
|
||||
|
||||
The Bender IsoCHA devices come with an internal 120 Ohms switchable bus termination resistor on the modbus connection terminals. To use it, put the switch into the upper (on) position.
|
||||
|
||||
Settings overwritten by the driver
|
||||
----------------------------------
|
||||
|
||||
During initialization, this driver overwrites the following settings:
|
||||
|
||||
* set "pre-alarm" resistor R1 (default = 600k) [register 3005 and following]
|
||||
* set "alarm" resistor R2 to slightly lower than R1 (= -10k) [register 3007]
|
||||
* disable low-voltage alarm [register 3008 and following]
|
||||
* disable overvoltage alarm [register 3010 and following]
|
||||
* set mode to "dc" [register 3023 and following]
|
||||
* disable automatic self-tests [register 3021 and following]
|
||||
* disable line voltage test [register 3024]
|
||||
* disable device (only if the configuration option ``threshold_resistance_kohm`` is set to its maximum of 600 [k Ohms]) [register 3026]
|
||||
|
||||
Startup and operation
|
||||
=====================
|
||||
|
||||
To start the device and begin insulation (and voltage) measurements, send a "start" command via the device's MQTT interface. The device will then begin sending its measurement data once a second.
|
||||
|
||||
After the desired measurement has been retrieved, disable the device via an MQTT "stop" command on its interface.
|
||||
|
||||
Devices with firmware version newer than 5.00 support a faster self test mode to reduce CableCheck time. This will automatically be used if supported by firmware.
|
||||
|
||||
Using the internal alarm functions and relays
|
||||
=============================================
|
||||
|
||||
The external alarm relays should be used to ensure shut down of the DC HV voltage independently from the Linux host. Make sure to configure the thresholds correctly.
|
||||